‘K’ Rated Isolation Transformer are designed to reduce the heating effect of harmonic currents produced by non-linear loads. A standard transformer is design based on resistive load calculation and will overheat and fail prematurely when connected to Non - linear loads.
K- Factor is defined as a ratio between the additional losses due to harmonics and the resistive losses at 50 Hz.Transformers with a rated K-factor of 4, 7, 13, 20 and 30 are available. The ANSI/ IEEE C57. 110 has derived a system of weighing how much harmonic load currents a Transformer can handle without exceeding its maximum temperature rise level.
A ‘K’ factor of 1 indicates no harmonics, while a K factor of 50 is the harshest harmonic environment possible. Typically a K Factor of 13 is sufficient for most applications. K factor must be determined to calculate the right size transformer that is needed.
UPS | Telecommunication Equipment’s | VFD’S / Drives |
Data centers, Call Centers, IT sector | Induction Heaters / Inverters | Plastic Industries |
Robotics | CNC Machines | Textile Machinery. |
Injection Moulding Machine | Pharmaceutical Machine | Food / Dairy Industries |
Sophisticated Equipment’s | Compressors | Assembly Line |
Parameter | Description |
KVA Rating – Three Phase | 10 to 2500 KVA |
Cooling | Air & Oil Cooled. |
Impedance | 3 - 4 % or as required. |
Input Voltage | 380 / 400 / 415 / 440 - 3 Phase or as required. |
Output Voltage | 380/400/415 / 200 / 220 V 3 Phase or as required. |
Input / Output configuration | Dyn11 standard / Zig Zag & other Vector Group on request. |
Construction | Double wound, Common core, Varnish and vacuum impregnated. |
Winding | Electrolytic grade Copper / Aluminum |
Neutral Conductor Rating | 200 % |
Frequency | 50 +/- 3 Hz / 60 Hz on request. |
Insulation Class / Level | H Class / 180 deg. C |
Maximum temperature rise | 115 deg. C. |
Efficiency | Better than 96 %. |
Regulation | 2 – 4 % or as required. |
Common mode Noise Attenuation | 60 – 80 dB / other on request. |
High Voltage Breakdown Test | 2.5 KV for one Minute Between windings and Earth. |
Termination Type | Terminal Board / Stud – Bolts / Bus Bar |
Enclosure Protection Class | IP21 / As per Requirement. |
Environment | Temperature Range 0 to 45 °C. Suitable for indoor Tropical use 90% RH (non-condensing). |
Reference Standard | IS2026 / IS11171 UL-1561 |
Life Expectancy | 25 Years |