‘K’ Rated Isolation Transformer

‘K’ Rated Isolation Transformer are designed to reduce the heating effect of harmonic currents produced by non-linear loads. A standard transformer is design based on resistive load calculation and will overheat and fail prematurely when connected to Non - linear loads.
K- Factor is defined as a ratio between the additional losses due to harmonics and the resistive losses at 50 Hz.Transformers with a rated K-factor of 4, 7, 13, 20 and 30 are available. The ANSI/ IEEE C57. 110 has derived a system of weighing how much harmonic load currents a Transformer can handle without exceeding its maximum temperature rise level.
A ‘K’ factor of 1 indicates no harmonics, while a K factor of 50 is the harshest harmonic environment possible. Typically a K Factor of 13 is sufficient for most applications. K factor must be determined to calculate the right size transformer that is needed.

UPS Telecommunication Equipment’s VFD’S / Drives
Data centers, Call Centers, IT sector Induction Heaters / Inverters Plastic Industries
Robotics CNC Machines Textile Machinery.
Injection Moulding Machine Pharmaceutical Machine Food / Dairy Industries
Sophisticated Equipment’s Compressors Assembly Line
Parameter Description
KVA Rating – Three Phase 10 to 2500 KVA
Cooling Air & Oil Cooled.
Impedance 3 - 4 % or as required.
Input Voltage 380 / 400 / 415 / 440 - 3 Phase or as required.
Output Voltage 380/400/415 / 200 / 220 V 3 Phase or as required.
Input / Output configuration Dyn11 standard / Zig Zag & other Vector Group on request.
Construction Double wound, Common core, Varnish and vacuum impregnated.
Winding Electrolytic grade Copper / Aluminum
Neutral Conductor Rating 200 %
Frequency 50 +/- 3 Hz / 60 Hz on request.
Insulation Class / Level H Class / 180 deg. C
Maximum temperature rise 115 deg. C.
Efficiency Better than 96 %.
Regulation 2 – 4 % or as required.
Common mode Noise Attenuation 60 – 80 dB / other on request.
High Voltage Breakdown Test 2.5 KV for one Minute Between windings and Earth.
Termination Type Terminal Board / Stud – Bolts / Bus Bar
Enclosure Protection Class IP21 / As per Requirement.
Environment Temperature Range 0 to 45 °C. Suitable for indoor Tropical use 90% RH (non-condensing).
Reference Standard IS2026 / IS11171 UL-1561
Life Expectancy 25 Years
  • Medical Diagnostic Equipment
  • Electronic Equipment
  • Lab Equipment
  • Pharmaceuticals Machine
  • Textile Machinery
  • Process Controls
  • Elevators
  • Cold Storage
  • Hospitals
  • Residential
  • Reduces the heating effect of harmonic currents produced by non-linear loads.
  • Due to double shielding technic, common mode noise attenuation is good and Protect UPS, Sophisticated Equipment’s / Machines, Telecommunications equipment from damage due to electrical noise, Surges / spikes etc.
  • Lower leakage current and Output Impedance.
  • Coil design is optimized for low eddy current loss, high permeability, low losses electrical steel, reduced flux densities to compensate for harmonic voltage distortion and high harmonic current carrying capacity.
  • 200 % Neutral current carrying capacity.
  • Isolation between a source and equipment ensures the improved safety of the Operator and equipment’s.
  • Reduced Surges and Spikes, High frequency Noise Reduction with double Shielding technique.